| 1 | +# DEVICE:COMMENT: |
| 2 | +# Device dump generated by ./nut-ddl-dump.sh on Wed, 26 Nov 2025 21:26:38 +0200 |
| 3 | +# DEVICE:EOC |
| 4 | + |
| 5 | +# :; upsc Eaton9E2000i@127.0.0.1 |
| 6 | +battery.capacity: 7.00 |
| 7 | +battery.charge: 100 |
| 8 | +battery.charge.low: 20 |
| 9 | +battery.charge.restart: 0 |
| 10 | +battery.charger.type: Constant Charge (CC) |
| 11 | +battery.protection: yes |
| 12 | +battery.runtime: 3353 |
| 13 | +battery.runtime.low: 180 |
| 14 | +battery.type: PbAc |
| 15 | +battery.voltage: 83.0 |
| 16 | +battery.voltage.nominal: 72 |
| 17 | +device.mfr: EATON |
| 18 | +device.model: 9E2000i |
| 19 | +device.serial: GE16F43216 |
| 20 | +device.type: ups |
| 21 | +device.usb.version: 01.29 |
| 22 | +driver.debug: 0 |
| 23 | +driver.flag.allow_killpower: 0 |
| 24 | +driver.name: usbhid-ups |
| 25 | +driver.parameter.interrupt_pipe_no_events_tolerance: -1 |
| 26 | +driver.parameter.pollfreq: 30 |
| 27 | +driver.parameter.pollinterval: 2 |
| 28 | +driver.parameter.port: auto |
| 29 | +driver.parameter.synchronous: auto |
| 30 | +driver.state: quiet |
| 31 | +driver.version: 2.8.4.787-787+gf8ecd520a |
| 32 | +driver.version.data: MGE HID 1.57 |
| 33 | +driver.version.internal: 0.71 |
| 34 | +driver.version.usb: libusb-1.0.29 (API: 0x0100010A) |
| 35 | +experimental.ups.mode.buzzwords: vendor:mge-hid:ECO vendor:default:ECO |
| 36 | +input.bypass.frequency: 49.9 |
| 37 | +input.bypass.switch.off: disabled |
| 38 | +input.bypass.switch.on: disabled |
| 39 | +input.bypass.switchable: enabled |
| 40 | +input.bypass.voltage: 235.0 |
| 41 | +input.eco.switchable: ECO |
| 42 | +input.frequency: 49.9 |
| 43 | +input.frequency.nominal: 50 |
| 44 | +input.transfer.bypass.forced: enabled |
| 45 | +input.transfer.bypass.high: 264 |
| 46 | +input.transfer.bypass.low: 184 |
| 47 | +input.transfer.bypass.overload: enabled |
| 48 | +input.transfer.eco.high: 243 |
| 49 | +input.transfer.eco.low: 218 |
| 50 | +input.transfer.frequency.bypass.range: 10 |
| 51 | +input.transfer.frequency.eco.range: 5 |
| 52 | +input.transfer.high: 300 |
| 53 | +input.transfer.hysteresis: 10 |
| 54 | +input.transfer.low: 100 |
| 55 | +input.voltage: 235.0 |
| 56 | +input.voltage.nominal: 235 |
| 57 | +outlet.1.designator: AC OUTPUT |
| 58 | +outlet.1.protect.status: protected |
| 59 | +outlet.1.status: on |
| 60 | +outlet.desc: Main Outlet |
| 61 | +outlet.id: 0 |
| 62 | +outlet.switchable: no |
| 63 | +output.current: 1.40 |
| 64 | +output.frequency: 49.9 |
| 65 | +output.frequency.nominal: 50 |
| 66 | +output.voltage: 236.0 |
| 67 | +output.voltage.nominal: 230 |
| 68 | +ups.beeper.status: enabled |
| 69 | +ups.delay.shutdown: 20 |
| 70 | +ups.delay.start: 30 |
| 71 | +ups.firmware: 00.02.000 |
| 72 | +ups.load: 17 |
| 73 | +ups.load.high: 105 |
| 74 | +ups.mfr: EATON |
| 75 | +ups.model: 9E2000i |
| 76 | +ups.power: 340 |
| 77 | +ups.power.nominal: 2000 |
| 78 | +ups.productid: ffff |
| 79 | +ups.realpower: 296 |
| 80 | +ups.realpower.nominal: 1600 |
| 81 | +ups.serial: GE16F43216 |
| 82 | +ups.shutdown: enabled |
| 83 | +ups.start.auto: yes |
| 84 | +ups.start.battery: yes |
| 85 | +ups.start.reboot: yes |
| 86 | +ups.status: OL |
| 87 | +ups.temperature: 24.9 |
| 88 | +ups.test.interval: 604800 |
| 89 | +ups.test.result: Done and passed |
| 90 | +ups.timer.shutdown: -1 |
| 91 | +ups.timer.start: -1 |
| 92 | +ups.type: online |
| 93 | +ups.vendorid: 0463 |
| 94 | + |
| 95 | +# DEVICE:COMMENT-BLOCK:FIXME:UPSRW: Eaton9E2000i@127.0.0.1 |
| 96 | +# [battery.charge.low] |
| 97 | +# Remaining battery level when UPS switches to LB (percent) |
| 98 | +# Type: STRING |
| 99 | +# Maximum length: 5 |
| 100 | +# Value: 20 |
| 101 | +# |
| 102 | +# [battery.charge.restart] |
| 103 | +# Minimum battery level for restart after power off (percent) |
| 104 | +# Type: STRING |
| 105 | +# Maximum length: 3 |
| 106 | +# Value: 0 |
| 107 | +# |
| 108 | +# [battery.protection] |
| 109 | +# Prevent deep discharge of battery |
| 110 | +# Type: STRING |
| 111 | +# Maximum length: 5 |
| 112 | +# Value: yes |
| 113 | +# |
| 114 | +# [battery.runtime.low] |
| 115 | +# Remaining battery runtime when UPS switches to LB (seconds) |
| 116 | +# Type: STRING |
| 117 | +# Maximum length: 10 |
| 118 | +# Value: 180 |
| 119 | +# |
| 120 | +# [driver.debug] |
| 121 | +# Current debug verbosity level of the driver program |
| 122 | +# Type: NUMBER |
| 123 | +# Value: 0 |
| 124 | +# |
| 125 | +# [driver.flag.allow_killpower] |
| 126 | +# Safety flip-switch to allow the driver daemon to send UPS shutdown command (accessible via driver.killpower) |
| 127 | +# Type: NUMBER |
| 128 | +# Value: 0 |
| 129 | +# |
| 130 | +# [input.bypass.switch.off] |
| 131 | +# Take the UPS out of Bypass mode |
| 132 | +# Type: STRING |
| 133 | +# Maximum length: 12 |
| 134 | +# Value: disabled |
| 135 | +# |
| 136 | +# [input.bypass.switch.on] |
| 137 | +# Put the UPS in Bypass mode |
| 138 | +# Type: STRING |
| 139 | +# Maximum length: 8 |
| 140 | +# Value: disabled |
| 141 | +# |
| 142 | +# [input.bypass.switchable] |
| 143 | +# Input auto transfer on Bypass when overload or out of tolerance (enabled or disabled) |
| 144 | +# Type: STRING |
| 145 | +# Maximum length: 8 |
| 146 | +# Value: enabled |
| 147 | +# |
| 148 | +# [input.eco.switchable] |
| 149 | +# Input High Efficiency (aka ECO) mode switch |
| 150 | +# Type: STRING |
| 151 | +# Maximum length: 8 |
| 152 | +# Value: ECO |
| 153 | +# |
| 154 | +# [input.transfer.bypass.forced] |
| 155 | +# Rule for allow auto Bypass switch (on/off) transfer modes (enabled or disabled) |
| 156 | +# Type: STRING |
| 157 | +# Maximum length: 8 |
| 158 | +# Value: enabled |
| 159 | +# |
| 160 | +# [input.transfer.bypass.high] |
| 161 | +# High voltage Bypass transfer point (V) |
| 162 | +# Type: STRING |
| 163 | +# Maximum length: 5 |
| 164 | +# Value: 264 |
| 165 | +# |
| 166 | +# [input.transfer.bypass.low] |
| 167 | +# Low voltage Bypass transfer point (V) |
| 168 | +# Type: STRING |
| 169 | +# Maximum length: 5 |
| 170 | +# Value: 184 |
| 171 | +# |
| 172 | +# [input.transfer.bypass.overload] |
| 173 | +# Rule for auto transfer on Bypass when overload (enabled or disabled) |
| 174 | +# Type: STRING |
| 175 | +# Maximum length: 8 |
| 176 | +# Value: enabled |
| 177 | +# |
| 178 | +# [input.transfer.eco.high] |
| 179 | +# High voltage ECO transfer point (V) |
| 180 | +# Type: STRING |
| 181 | +# Maximum length: 5 |
| 182 | +# Value: 243 |
| 183 | +# |
| 184 | +# [input.transfer.eco.low] |
| 185 | +# Low voltage ECO transfer point (V) |
| 186 | +# Type: STRING |
| 187 | +# Maximum length: 5 |
| 188 | +# Value: 218 |
| 189 | +# |
| 190 | +# [input.transfer.frequency.bypass.range] |
| 191 | +# Frequency range Bypass transfer point (percent of nominal Hz) |
| 192 | +# Type: STRING |
| 193 | +# Maximum length: 5 |
| 194 | +# Value: 10 |
| 195 | +# |
| 196 | +# [input.transfer.frequency.eco.range] |
| 197 | +# Frequency range ECO transfer point (percent of nominal Hz) |
| 198 | +# Type: STRING |
| 199 | +# Maximum length: 5 |
| 200 | +# Value: 5 |
| 201 | +# |
| 202 | +# [input.transfer.high] |
| 203 | +# High voltage transfer point (V) |
| 204 | +# Type: STRING |
| 205 | +# Maximum length: 5 |
| 206 | +# Value: 300 |
| 207 | +# |
| 208 | +# [input.transfer.hysteresis] |
| 209 | +# Threshold of switching protection modes, voltage transfer point (V) |
| 210 | +# Type: STRING |
| 211 | +# Maximum length: 5 |
| 212 | +# Value: 10 |
| 213 | +# |
| 214 | +# [input.transfer.low] |
| 215 | +# Low voltage transfer point (V) |
| 216 | +# Type: STRING |
| 217 | +# Maximum length: 5 |
| 218 | +# Value: 100 |
| 219 | +# |
| 220 | +# [outlet.desc] |
| 221 | +# Outlet description |
| 222 | +# Type: STRING |
| 223 | +# Maximum length: 20 |
| 224 | +# Value: Main Outlet |
| 225 | +# |
| 226 | +# [output.voltage.nominal] |
| 227 | +# Nominal output voltage (V) |
| 228 | +# Type: ENUM STRING |
| 229 | +# Maximum length: 3 |
| 230 | +# Option: "200" |
| 231 | +# Option: "208" |
| 232 | +# Option: "220" |
| 233 | +# Option: "230" SELECTED |
| 234 | +# Option: "240" |
| 235 | +# |
| 236 | +# [ups.delay.shutdown] |
| 237 | +# Interval to wait after shutdown with delay command (seconds) |
| 238 | +# Type: STRING |
| 239 | +# Maximum length: 10 |
| 240 | +# Value: 20 |
| 241 | +# |
| 242 | +# [ups.delay.start] |
| 243 | +# Interval to wait before (re)starting the load (seconds) |
| 244 | +# Type: STRING |
| 245 | +# Maximum length: 10 |
| 246 | +# Value: 30 |
| 247 | +# |
| 248 | +# [ups.load.high] |
| 249 | +# Load when UPS switches to overload condition (percent) |
| 250 | +# Type: STRING |
| 251 | +# Maximum length: 5 |
| 252 | +# Value: 105 |
| 253 | +# |
| 254 | +# [ups.shutdown] |
| 255 | +# Enable or disable UPS shutdown ability (poweroff) |
| 256 | +# Type: ENUM STRING |
| 257 | +# Maximum length: 10 |
| 258 | +# Option: "disabled" |
| 259 | +# Option: "enabled" SELECTED |
| 260 | +# |
| 261 | +# [ups.start.auto] |
| 262 | +# UPS starts when mains is (re)applied |
| 263 | +# Type: STRING |
| 264 | +# Maximum length: 5 |
| 265 | +# Value: yes |
| 266 | +# |
| 267 | +# [ups.start.battery] |
| 268 | +# Allow to start UPS from battery |
| 269 | +# Type: STRING |
| 270 | +# Maximum length: 5 |
| 271 | +# Value: yes |
| 272 | +# |
| 273 | +# [ups.start.reboot] |
| 274 | +# UPS reboots when power returns during shutdown delay |
| 275 | +# Type: STRING |
| 276 | +# Maximum length: 5 |
| 277 | +# Value: yes |
| 278 | +# |
| 279 | +# [ups.test.interval] |
| 280 | +# Interval between self tests (seconds) |
| 281 | +# Type: STRING |
| 282 | +# Maximum length: 8 |
| 283 | +# Value: 604800 |
| 284 | +# DEVICE:EOC |
| 285 | + |
| 286 | +# DEVICE:COMMENT-BLOCK:FIXME:UPSCMD: Eaton9E2000i@127.0.0.1 |
| 287 | +# Instant commands supported on UPS [Eaton9E2000i]: |
| 288 | +# |
| 289 | +# beeper.disable - Disable the UPS beeper |
| 290 | +# beeper.enable - Enable the UPS beeper |
| 291 | +# beeper.mute - Temporarily mute the UPS beeper |
| 292 | +# beeper.off - Obsolete (use beeper.disable or beeper.mute) |
| 293 | +# beeper.on - Obsolete (use beeper.enable) |
| 294 | +# bypass.start - Put the UPS in Bypass mode |
| 295 | +# bypass.stop - Take the UPS out of Bypass mode |
| 296 | +# driver.killpower - Tell the driver daemon to initiate UPS shutdown; should be unlocked with driver.flag.allow_killpower option or variable setting |
| 297 | +# driver.reload - Reload running driver configuration from the file system (only works for changes in some options) |
| 298 | +# driver.reload-or-error - Reload running driver configuration from the file system (only works for changes in some options); return an error if something changed and could not be applied live (so the caller can restart it with new options) |
| 299 | +# driver.reload-or-exit - Reload running driver configuration from the file system (only works for changes in some options); exit the running driver if something changed and could not be applied live (so service management framework can restart it with new options) |
| 300 | +# experimental.bypass.ecomode.start - Put UPS in Bypass mode then High Efficiency (aka ECO) mode |
| 301 | +# experimental.bypass.ecomode.stop - Take the UPS out of High Efficiency (aka ECO) mode after exiting Bypass mode |
| 302 | +# experimental.ecomode.start - Put UPS in High Efficiency (aka ECO) mode |
| 303 | +# experimental.ecomode.stop - Take the UPS out of High Efficiency (aka ECO) mode |
| 304 | +# experimental.essmode.start - Put UPS in Energy Saver System (aka ESS) mode |
| 305 | +# experimental.essmode.stop - Take the UPS out of Energy Saver System (aka ESS) mode |
| 306 | +# load.off - Turn off the load immediately |
| 307 | +# load.off.delay - Turn off the load with a delay (seconds) |
| 308 | +# load.on - Turn on the load immediately |
| 309 | +# load.on.delay - Turn on the load with a delay (seconds) |
| 310 | +# shutdown.default - Run the driver-defined UPS shutdown sequence (as opposed to user-configured 'sdcommands') |
| 311 | +# shutdown.return - Turn off the load and return when power is back |
| 312 | +# shutdown.stayoff - Turn off the load and remain off |
| 313 | +# shutdown.stop - Stop a shutdown in progress |
| 314 | +# test.battery.start.deep - Start a deep battery test |
| 315 | +# test.battery.start.quick - Start a quick battery test |
| 316 | +# test.battery.stop - Stop the battery test |
| 317 | +# DEVICE:EOC |