ARServer Smart Full Discovery Audit V3

Why MMXU2..MMXU24 could still be missing

The previous fixes were still too dependent on one high-level discovery artifact. If the first MMS GetNameList page was treated as final, a large IED could appear to expose only the early logical nodes, for example MMXU1, even though IEDScout continues browsing and shows MMXU2..MMXU24.

Fixes in this patch

  1. MMS GetNameList pagination fixed

    • MMS moreFollows has ASN.1 default TRUE.
    • ARServer previously treated an omitted moreFollows as FALSE.
    • That can stop discovery after page 1.
    • The decoder now defaults to TRUE and the session continues while new names are returned.
    • If a trailing page fails after names were already collected, ARServer keeps the collected names instead of throwing away the discovery result.
  2. GetVariableAccessAttributes type-tree expansion added

    • Supplemental clean-room discovery now calls MMS GetVariableAccessAttributes for discovered domain variables.
    • This expands LN/FC/DO/DA structure similarly to what an IED browser does.
    • Expanded names are merged into the native snapshot before signal mapping.
  3. No hardcoded MMXU instance range

    • This patch does not synthesize MMXU1..MMXU24 by range.
    • Logical node instances must come from MMS directory, variable attributes, report inventory, DataSet inventory, or ARIEC61850 live model objects.
  4. Wizard remains signal-centric

    • Report/DataSet selection is not a user decision in the wizard.
    • Step 3 is a read-only Auto Report Plan review.
    • Main toolbar button is renamed to Auto Plan.
  5. Selection workflow improved

    • Grid supports Extended row selection.
    • Header checkbox selects/deselects visible publishable signals.
    • Space toggles all highlighted rows.
    • Ctrl/Shift selection can be used before toggling.

Expected test result

For a Moxa/GD style IED that IEDScout shows with MMXU1..MMXU24, the wizard should now populate from the actual MMS directory/type tree. If it still shows only MMXU1, check the Native Discovery log:

  • If raw variables remain low, the IED is not returning the full directory to ARServer's MMS association.
  • If raw variables are high but SCADA candidates are low, the mapper still needs refinement.
  • If VAA/type-tree expansion errors appear, the next fix should focus on the MMS GetVariableAccessAttributes request/decoder profile for that IED.